XP6-R Six Relay Control Module
- NOTIFIER’s XP6-R six-relay control module provides an intelligent fire alarm system with six Form-C relays.
- The first module is addressed from 01 to 154 while the remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules. A single isolated set of dry relay contacts is provided for each module address, which is capable of being wired for either a normally-open or normally-closed operation. The module allows the control panel to switch these contacts on command. No supervision is provided for the controlled circuit.
• Six addressable Form-C relay contacts
• Removable 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²) plug-in terminal blocks
• Status indicators for each point
• Unused addresses may be disabled
• Rotary address switches
• FlashScan® or CLIP operation
• Mount one or two modules in a BB-XP cabinet (optional)
• Mount up to six modules on a CHS-6 chassis in a CAB-3 Series, CAB-4 Series, EQ Series, or BB-25 cabinet (optional)
• Mounting hardware included
- Standby current: 1.45 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases)
- Alarm current: 32 mA (assumes all six relays have been switched once and all six LEDs solid ON)
- Temperature range: 32°F to 120°F (0°C to 49°C)
- Humidity: 10% to 93% non-condensing
- Dimensions: 6.8" (17.27 cm) high x 5.8" (14.73 cm) wide x 1.0" (2.54 cm) deep
- Shipping weight: 1.1 lb. (0.5 kg) including packaging
- Mounting options: CHS-6 chassis, BB-25 cabinet, BB-XP cabinet, CAB-3 Series (see DN-3549) cabinet, CAB-4 Series (see DN-6857) cabinet, or EQ Series (see DN-60229) cabinet
- Wire gauge: 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²)
- Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent
- Relay current: 30 mA/relay pulse (15.6 ms pulse duration), pulse under panel control
- Relay contact ratings: 30 VDC; 70.7 VAC
• UL Listed: S635
• ULC Listed: S635 (XP6-RA)
• MEA Listed: 368-01-E
• CSFM: 7300-0028:0219
• Maryland State Fire Marshall: Permit # 2099
• FM Approved (Light Protective Signaling Only)