ISO-X Fault Isolator Module
General Description
- The Notifier ISO-X(A) Fault Isolator Module is used with Notifier Onyx and CLIP series Fire Alarm Control Panels (FACPs) to protect the system against wire-to-wire short circuits on the SLC loops.
- Powered by SLC loop directly, no external power required.
- Base mounts on standard junction boxes (4.0"/10.16 cmsquare by 2.125"/5.398 cm deep).
- Integral LED blinks to indicate normal condition. Illuminates steady when short circuit condition is detected.
- High noise (EMF/RFI) immunity.
- Wide viewing angle of LED.
- SEMS screws with clamping plates for ease of wiring.
- Opens SLC loop automatically on detection of short, preventing the short from causing failure of the entire loop.
- Automatically resets on correction of short.
- Supports Style 4, 6, or 7 wiring.
- Normal operating voltage: 15 – 32 VDC (peak).
- Standby current: 450 A (not isolating) .
- Maximum current draw: 17 mA (device in isolation, LED latched in alarm).
- Temperature range: 32°F to 120°F (0°C to 49°C).
- Relative humidity: 10% to 93% (non-condensing).
- Weight: 5 oz. (150 grams).
- Dimensions: 4.5”H x 4.5”W x 0.25” D (11.43 cm H x 11.43 cm W x 0.635 cm D).
• UL: S635 (UOXX); BP6480 (AMCX, APOU).
• ULC: S635 (OUOXXC, ISO-XA).
• FM Approved.
• CSFM: 7165-0028:0214; 7165-0028:0224; 7165- 0028:0243.
• MEA: 17-96-E; 104-93-E Vol. VI; 290-91-E Vol. V; 317-01- E; 447-99-E.
• U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• BSA: 578-81-SA.