  • The RP-2002 is a six-zone FACP for single and dual hazard agent releasing applications. The RP-2002 provides reliable fire detection, signaling and protection for commercial, industrial and institutional buildings requiring agent-based releasing. The RP-2002 is compatible with System Sensor’s i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45°F (7.22°C). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Notifier Device Compatibility Document for a complete listing of compatible devices.

• Listed to UL Standard 864, 9th edition.
• FM Approved.
• Designed for agent releasing standards NFPA 12, 12A,12B, and 2001.
• Meets International Building Code (IBC) seismic requirements.
• Disable/Enable control per input zone and output zone.
• Extensive transient protection.
• Dual hazard operation.
• Adjustable pre-discharge, discharge and waterflow delay timers.
• Cross-zone (double-interlock) capability.
• Six programmable Style B (Class B) IDCs (Initiating Device Circuit).
• System Sensor i3 series detector compatible.
• Four programmable Style Y (Class B) output circuits - (special application power).
Strobe synchronization:
– System Sensor

– Wheelock

– Gentex
– Faraday
– Amseco
• Three programmable Form-C relays.
• 7.0 amps total 24 VDC output current.
• Resettable and non-resettable output power.
• Built-in Programmer.
ANN-BUS connector for communication with optional devices (up to 8 total of any of the following)
– N-ANN-80 Remote LCD Annunciator
– N-ANN-I/O LED Driver
– N-ANN-S/PG Printer Modules
– N-ANN-RLY Relay Module
– N-ANN-LED Annunciator Module
• 80-character LCD display (backlit).
• Real-time clock/calendar with daylight savings time control.
• History log with 256 event storage.
• Piezo sounder for alarm, trouble and supervisory.
• 24 volt operation.
• Low AC voltage sense.
Outputs Programmable for
– Releasing Circuits or NACS
NACs programmable for
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Non-silenceable

– Release Stage Sounder

• Automatic battery charger with charger supervision.
• Optional Dress Panel DP-51050 (red).
• Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet.
• Optional N-CAC-5X Class A Converter Module for Outputs and IDCs.
• Optional 4XTM Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD, 411UDAC).
• Optional ANN-SEC card for a secondary ANN-BUS.

 

• RP-2002 (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66 amps
• RP-2002E (FLPS-7 Power Supply): 240 VAC, 50/60 Hz, 2.085 amps
• Wire size: minimum 14 AWG (2.0 mm²) with 600 V insulation, supervised, nonpower-limited Cabinet Specifications

 

• UL: S635
• FM approved
• CSFM: 7165-0028:0245
• MEA: 333-07-E
• Seismic Listing: Reference certificiate of compliance VMA - 45894-01 by the VMC Group