SFP-2402 2-Zone Fire Alarm Control Panel
- The Notifier SFP-2402 and SFP-2402E Fire Alarm Control Panels (FACPs) bring the latest in microprocessor technology to conventional fire controls. The SFP-2402 is compatible with the i³™ smoke detectors from System Sensor with drift compensation, maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices with three selections for manufacturer protocol. The Notification Appliance Circuit (NAC) protocol can silence audible devices while strobes continue to flash, using a single pair of wires.
• Two Style B (Class B) Initiating Device Circuits (IDCs).
• One Style Y (Class B) NAC.
• 24 VDC.
i³™ Technology features:
– Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused by dust accumulation.
– Maintenance Alert LEDs (per zone) warn of excessive dirt accumulation, preventing false alarms (meets NFPA 72 requirements).
– Detector sensitivity is automatically measured by the detector, which automatically adjusts its sensitivity back to the factory settings when it becomes more sensitive due to contaminants settling in the chamber.
– Wireless handheld sensitivity meter eliminates the need for voltmeters, magnets, and a physical connection to the detector. The reader displays sensitivity in terms of percent per foot obscuration and provides text status indication.
– Supervisory LED (per zone) provides warning if a detector senses temperature approaching freezing.
– Special test protocol and LED indication allows quick test of all detectors without need for a ladder.
NAC synchronization features:
– Synchronization of standard ANSI audible signals
AC POWER — TB8
• SFP-2402: 120 VAC, 50/60 Hz, 2.3 A.
• SFP-2402E: 240 VAC, 50 Hz, 1.15 A.
• Wire Size: Minimum 14 AWG (2.0 mm²) with 600 V insulation.
BATTERY (SEALED LEAD-ACID ONLY) — J8
• Maximum charging circuit: normal flat charge 27.6 VCD @0.8 A.
• Maximum battery charger capacity: 18.0 AH battery
(two 7.0 AH batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the Notifier BB-17). INITIATING DEVICE CIRCUIT — TB3
• Alarm zones 1 & 2.
• Power-limited circuitry.
• Operation: all zones Style B (Class B).
• Normal operating voltage: nominal 20 VDC.
• Alarm current: 15 mA minimum.
• Short-circuit current: 40 mA maximum.
• Maximum loop resistance: 100 ohms.
• End-of-line resistor: 4.7K ohm, ½ watt (P/N 71252).
• Standby current: 4 mA.
• Compatible devices: refer to the Notifier Device Compatibility
Document no. 15378 for a complete list of compatibledevices.
• UL Listed: S635.
• MEA: 297-01-E Vol. II.
• CSFM: 7165-0028:220.