Registered firefighters 1, 2, and 3 equipment contractors
Registered electrical contractor, registered plumbing contractor
Registered minor works contractor (Levels 2 and 3)
Competent persons for mandatory window inspection programs

Print this page

FLM-420-I8R1-S Octo-input interface module with relay

  • The FLM‑420‑I8R1‑S Octo-input Interface Module with Relay allows the monitoring of up to eight inputs. Additionally, it features a change‑over contact relay for providing a potential‑free output contact. It is a 2‑wire LSN element. When connected to the fire panels FPA‑5000 and FPA‑1200, the interface module offers the enhanced functionality of LSN improved technology.

 

  • Individually selectable monitoring functions (EOL or contact) for the eight inputs each 
  • Maximum switching capacity 2 A / 30 V DC or 0.5 A / 42.4 V AC 
  • Maintains LSN loop functions in the event of wire interruption or short-circuit thanks to two integrated isolators 
  • Easy wiring thanks to pluggable terminal blocks

 

   
LSN input voltage (V DC) 15 … 33
Max. current consumption from LSN (mA) 5.5
Inputs, independent 8
Line monitoring: EOL resistor, nominal (kΩ)Detected line conditions (Ω) with overall line resistance RΣ = RL/1 + RL/2 + REOL 3.9Standby: 1500 … 6000Interruption: > 12000Short circuit: < 800
Contact monitoring: Max. current consumption (mA) 8
Min. activation time of the inputs IN 1…8 (s) 3.2
Change-over relay, low voltage NC / COM, COM / NO
Contact load: Max. switching capacity (A / V DC; A / V AC)Min. switching capacity (mA / mV DC; mA / mV AC) Max. frequency (Hz) 2 / 30; 0.5 / 42.40.01 / 10; 0.01 / 10100
   
Connections Screw terminals 
Rotary switches, number 3
Weight, without/with packing (g) 480 / 800
Dimensions W x H x D (mm) 140 x 200 x 48 
Wire gauge (mm2) 0.6…3.3
Housing material, housing color (RAL) ABS+PC-FR, RAL 9003
   
Operating temperature (°C) -20 …+65 
Storage temperature (°C) -25 …+80 
Rel. humidity (%), non-condensing < 96 %
Class of equipment (IEC 60950) III
Degree of protection (IEC 60529) IP 54
   
Max. cable length, not electrically isolated from LSN in total (m) 500
<12>

 

 

 