FZM-1 2-Wire Detector Module
General Description
- Four different monitor modules are available for Notifier’s intelligent control panels for a variety of applications. Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors
- FZM-1(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit.
- Supports compatible two-wire smoke detectors.
- Supervises IDC wiring and connection of external power source.
- High noise (EMF/RFI) immunity.
- SEMS screws with clamping plates for ease of wiring.
- Direct-dial entry entry of address: 01 – 159 on FlashScan loops, 01 – 99 on CLIP loops.
- LED flashes during normal operation; this is a programmable option.
- LED latches steady to indicate alarm on command from control panel.
- Nominal operating voltage: 15 to 32 VDC.
- Maximum current draw: 5.1 mA (LED on).
- Maximum IDC wiring resistance: 25 Ohms.
- Average operating current: 270 μA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol.
- EOL resistance: 3.9K Ohms.
- External supply voltage (between Terminals T10 and T11):
- DC voltage: 24 volts power limited.
- Ripple voltage: 0.1 Vrms maximum.
- Current: 90 mA per module maximum.
- Temperature range: 32°F to 120°F (0°C to 49°C).
• UL: S635.
• ULC: S635.
• FM Approved.
• CSFM: 7300-0028:0219, 7165-0028:0224,7165-0028:0243.
• MEA: 457-99-E.
• U.S. Coast Guard: 161.002/50/0 (NFS2-640, NFS2-320, NFS2-3030).
• Lloyd’s Register: 11/600013 (NFS2-640, NFS2-320, NFS2-3030).
• Fire Dept. of New York: COA #6121 (NFS2-640, NFS- 320), COA# 6114 (NFS2-3030).