Registered firefighters 1, 2, and 3 equipment contractors
Registered electrical contractor, registered plumbing contractor
Registered minor works contractor (Levels 2 and 3)
Competent persons for mandatory window inspection programs

Print this page

FRM-1 Relay Module

  • FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay Module provides the system with a dry-contact output for activatinga variety of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis.

 

  • Built-in type identification automatically identifies these devices to the control panel.
  • Internal circuitry and relay powered directly by two-wire SLC loop. The FCM-1(A) module requires power (for horns, strobes, etc.), or audio (for speakers).
  • Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated.
  • LED blink may be deselected globally (affects all devices).
  • High noise immunity (EMF/RFI).
  • The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms).
  • Wide viewing angle of LED.
  • SEMS screws with clamping plates for wiring ease.
  • Direct-dial entry of address 01– 159 for FlashScan loops, 01 – 99 for CLIP mode loops.
  • Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z).
  • The FRM-1(A) provides two Form-C dry contacts thatswitch together.

 

Download

FMM-1 Monitor Module

 

 

 

 

  • Normal operating voltage: 15 to 32 VDC.
  • Maximum current draw: 6.5 mA (LED on).
  • Average operating current: 230 A direct poll; 255 A group poll.
  • EOL resistance: not used.
  • Temperature range: 32°F to 120°F (0°C to 49°C).
  • Humidity range: 10% to 93% non-condensing.
  • Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box.
  • Accessories: SMB500 Electrical Box; CB500 Barrier

 

• UL: S635
• ULC: S3705 (A version only)
• FM Approved
• CSFM: 7300-0028:0219
• MEA: 14-00-E
• FDNY: COA #6067, #6065