FSP-851 Smoke Detector
- Notifier FSP-851(A) Series intelligent plug-in smoke detectors with integral communication provide features that surpass conventional detectors. Detector sensitivity can be programmed in the control panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector’s address to be set with rotary,decimal address switches,providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level.
- The FSP-851(A) photoelectric detector’s unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixedtemperature thermal sensing on the FSP -851T(A). The FSP-851R(A) is a remote test capable detector for use with DNR(A)/DNRW duct detector housings. FSP-851(A) series detectors are compatible with Notifier Onyx and CLIP series Fire Alarm Control Panels (FACPs).
• Sleek, low-profile design.
• Addressable-analog communication.
• Stable communication technique with noise immunity.
• Low standby current.
• Two-wire SLC connection.
• Compatible with FlashScan® and CLIP protocol systems.
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on FlashScan systems).
• Optional remote, single-gang LED accessory.
• Dual LED design provides 360° viewing angle.
• Visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan systems only).
• Remote test feature from the panel.
• Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(FlashScan systems only).
• Built-in functional test switch activated by external magnet.
• Built-in tamper-resistant feature.
• Sealed against back pressure.
• Constructed of off-white fire-resistant plastic, designed to commercial standards, and offers an attractive appearance.
• 94-5V plastic flammability rating.
• SEMS screws for wiring of the separate base.
• Optional relay, isolator, and sounder bases.
Sensitivity: 0.5% to 2.35% per foot obscuration
Size: 2.1" (5.3 cm) high; base determines diameter.
- B210LP(A): 6.1" (15.5 cm) diameter.
- B501(A): 4.1" (10.4 cm) diameter.
- B200S(A): 6.875" (17.46 cm) diameter.
- B200SR(A): 6.875" (17.46 cm) diameter.
- B224RB(A): 6.2" (15.748 cm) diameter.
- B224BI(A): 6.2" (15.748 cm) diameter.
Shipping Weight: 5.2oz. (147g).
- Operating Temperature range: FSP-851(A), 0°C to 49°C(32°F to 120°F). FSP-851T(A), 0°C to 38°C (32°F to100°F).Lowtemperature signal for FSP-851T(A) at 45°F +/- 10°F(7.22°C +/- 5.54°C). FSP-851R(A) installed in a DNR(A)/ DNRW, -20°C to 70°C (-4°F to 158°F).
- UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts.
- Relative Humidity: 10%-93% noncondensing.
- Thermal Ratings: Fixed-temperature setpoint 135°F (57°C).
DETECTOR SPACING AND APPLICATIONS
- Notifier recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling,space detectors 30 feet (9.144m) for ceiling heights 10 feet (3.148m) and higher. For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. System Smoke Detector Application Guide, document A05-1003, is available at systemsensor.com
- ELECTRICAL SPECIFICATIONS
- Voltage Range: 15-32 volts DC peak.
- Standby Current (max. avg.): 300μA @ 24VDC (one communication every five seconds with LED enabled).
- LED Current (max.): 6.5mA @ 24 VDC (“ON”).
• UL Listed: S1115.
• ULC Listed: S1115 (FSP-851A, FSP-851RA, FSP-851TA).
• MEA Listed: 225-02-E .
• FM Approved.
• CSFM: 7272-0028:0206 .
• Maryland State Fire Marshal: Permit # 2122 .
• BSMI: CI313066760036.
• CCCF: Certif. # 2004081801000017 (FSP-851T)Certif. # 2004081801000016 (FSP-851).
• U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).