- MAYSUN ENGINEERING COMPANY LIMITED - https://maysun.com.hk -

NFS2-3030 Intelligent Addressable Fire Alarm System

  • General Description

    • The NFS2-3030 is an intelligent Fire Alarm Control Panel (FACP) designed for medium- to large-scale facilities. Fire emergency detection and evacuation are extremely critical to life safety, and the NFS2-3030 is ideally suited for these applications.
    • The NFS2-3030 is part of the ONYX® Series of products from NOTIFIER. The NFS2-3030 is ideal for virtually any application because it features a modular design that is configured per project requirements. With one to ten Signaling Line Circuits (SLCs), the NFS2-3030 supports up to 3,180 intelligent addressable devices. Information is critical to fire evacuation personnel, and the NFS2-3030’s large 640-character Liquid Crystal Display (LCD) presents vital information to operators concerning a fire situation, fire progression, and evacuation details. A host of other options are available, including single- or multichannel voice; firefighter’s telephone; LED, LCD, or PC-based graphic annunciators; networking; advanced detection products for challenging environments; wireless fire protection; andmany additional options.

    本頁圖片/檔案 - notifier-nfs2-3030-c-2013

     

     

  • Features

    • Certified for seismic applications when used with the appropriate seismic mounting kit.
    • Approved for Marine applications when a marine-listed version is used with marine-listed compatible equipment. See DN-60688.
    • Complies with UL 2572 Mass Notification Systems (NFS2- 3030 version 20 or higher).
    • One to ten isolated intelligent Signaling Line Circuits (SLC) Style 4, 6 or 7.
    • Wireless fire protection using SWIFT Smart Wireless Integrated Fire Technology. See DN-60820.
    • Up to 159 detectors and 159 modules per SLC; 318 devices per loop/3,180 per FACP or network node.
    – Detectors can be any mix of ion, photo, thermal, or multisensor; wireless detectors are available for use with the FWSG.
    – Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or relay; wireless modules are available for use with the FWSG.
    • Large 16 line, 640 character LCD backlit display or use display-less as a network node.
    • Network options:
    – High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NFS-3030, NFS-640, and NCA).
    – Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes
    when DVC-EM is used in network paging.
    • Built-in Alarm, Trouble, Security, and Supervisory relays.

    • VeriFire® Tools online/offline program option.

    • With built-in Degraded Mode operation, the system is capable of general alarm if a fire alarm condition is present even if the central processing unit (CPU) fails.
    • Weekly Occupancy Schedules allow changing sensitivity by time of day and day of week.
    • EIA-485 annunciators, including custom graphics.
    • History file with 4000-event capacity in nonvolatile memory, plus separate 1000-event alarm-only file.
    • Advanced history filters allow sorting by event, time, date, or address.
    • Alarm Verification selection per point, with automaticcounter.
    • Autoprogramming and Walk Test reports.
    • Multiple central station communication options:
    – Standard UDACT
    – Internet
    – Internet/GSM
    • Positive Alarm Sequence (PAS) Presignal.
    • Silence Inhibit and Auto Silence timer options.
    • Field-programmable on panel or on PC, with VeriFire Tools program, also check, compare.
    • Non-alarm points for lower priority functions.
    • Remote ACK/Signal Silence/System Reset/Drill via monitor modules.
    • Up to 1000 powerful Boolean logic equations.
    • Supports SCS Series smoke control system in both HVAC and FSCS modes.
    • FM6320 approved Gas Detection System with FMM-4-20 module and any FM listed gas detector.

    • EIA-232 printer port.
    • EIA-485 annunciator port.

     

  • Data Sheet

    Download

    NFS2-3030 Intelligent Addressable Fire Alarm System

     

     

     

     

     

  • Specification

    SYSTEM CAPACITY
    • Intelligent Signaling Line Circuits ...........1 expandable to 10
    • Intelligent detectors .......................................... 159 per loop
    • Addressable monitor/control modules .............. 159 per loop
    • Programmable software zones............................. over 2000
    • ACS annunciators per CPU2-3030 .......................32 address x 64 or 96 points
    NOTE: The CPU2-3030 can support up to 96 annunciator address points per ACM-24AT/-48A.
    SPECIFICATIONS
    Primary Input Power:
    – AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum.
    – AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum

    DC Output:
    – Main 24 VDC: Up to 5.0 A
    – Aux 24 VDC: Up to 5.0 A
    – 5 VDC: Up to 0.15 A.
    Current draw (Standby/Alarm):
    – CPU2-3030D board: 0.340 A.
    – CPU2-3030ND board: 0.120 A.
    – LCM-320: 0.130 A.
    – LEM-320: 0.100 A.

    – AMPS-24(E)*: 0.13 A.
    (Draws power from secondary power source only.)

     

  • Certification

    • UL Listed: S635.
    • ULC Listed: S527-11.
    • MEA: 232-06-E.
    • Fire Dept. of New York: COA#6211.
    • CSFM: 7165-0028:0224 (Commercial).
    • FM Approved.
    • FM6320 Approved. Class 6320 for Gas Detection.
    • City of Chicago.
    • City of Denver.
    • Singapore Productivity and Standards Board (PSB).
    • CCCF listed.
    • Fire Services Department (Hong Kong).

     

     


Article printed from MAYSUN ENGINEERING COMPANY LIMITED : https://maysun.com.hk

URL to article: https://maysun.com.hk/en/print_page/product_details/89