XP6-R Six Relay Control Module

  • General Description

    • NOTIFIER’s XP6-R six-relay control module provides an intelligent fire alarm system with six Form-C relays.
    • The first module is addressed from 01 to 154 while the remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules. A single isolated set of dry relay contacts is provided for each module address, which is capable of being wired for either a normally-open or normally-closed operation. The module allows the control panel to switch these contacts on command. No supervision is provided for the controlled circuit.

     

     

     

  • Features

    • Six addressable Form-C relay contacts
    • Removable 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²) plug-in terminal blocks
    • Status indicators for each point
    • Unused addresses may be disabled
    • Rotary address switches
    • FlashScan® or CLIP operation
    • Mount one or two modules in a BB-XP cabinet (optional)
    • Mount up to six modules on a CHS-6 chassis in a CAB-3 Series, CAB-4 Series, EQ Series, or BB-25 cabinet (optional)
    • Mounting hardware included

     

  • Data Sheet

    Download

    XP6-R Six Relay Control Module

     

     

     

     

  • Specification

    • Standby current: 1.45 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases)
    • Alarm current: 32 mA (assumes all six relays have been switched once and all six LEDs solid ON)
    • Temperature range: 32°F to 120°F (0°C to 49°C)
    • Humidity: 10% to 93% non-condensing
    • Dimensions: 6.8" (17.27 cm) high x 5.8" (14.73 cm) wide x 1.0" (2.54 cm) deep
    • Shipping weight: 1.1 lb. (0.5 kg) including packaging
    • Mounting options: CHS-6 chassis, BB-25 cabinet, BB-XP cabinet, CAB-3 Series (see DN-3549) cabinet, CAB-4 Series (see DN-6857) cabinet, or EQ Series (see DN-60229) cabinet
    • Wire gauge: 12 AWG (3.25 mm²) to 18 AWG (0.9 mm²)
    • Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent
    • Relay current: 30 mA/relay pulse (15.6 ms pulse duration), pulse under panel control
    • Relay contact ratings: 30 VDC; 70.7 VAC

     

  • Certification

    • UL Listed: S635
    • ULC Listed: S635 (XP6-RA)
    • MEA Listed: 368-01-E
    • CSFM: 7300-0028:0219
    • Maryland State Fire Marshall: Permit # 2099
    • FM Approved (Light Protective Signaling Only)

     

     