XP10-M Ten-Input Monitor Module

  • General Description

    • The XP10-M ten-input monitor module is an interface between a control panel and normally open contact devices in intelligent alarm systems such as pull stations, security contacts, or flow switches.
    • The first address on the XP10-M is set from 01 to 150 and the remaining modules are automatically assigned to the next nine higher addresses. Provisions are included for disabling a maximum of two unused addresses.

     

  • Features

    • Listed to UL Standard 864, 9th edition.
    • Ten addressable Class B or five addressable Class A initiating device circuits.
    • Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²) plug-in terminal blocks.
    • Status indicators for each point.
    • Unused addresses may be disabled.
    • Rotary address switches.
    • Class A or Class B operation.
    • FlashScan® or CLIP operation.
    • Flexible mounting options.
    • Mounting hardware included.

     

     

  • Data Sheet

    Download

    XP10-M Ten-Input Monitor Module

     

     

     

     

  • Specification

    • Standby current: 3.5 mA (SLC current draw with all addresses used; if some addresses are disabled, the standby current decreases).
    • Alarm current: 55 mA (assumes all ten LEDs solid ON).
    • Temperature range: 32°F to 120°F (0°C to 49°C) for UL applications; –10°C to +55°C for EN54 applications.
    • Humidity: 10% to 85% noncondensing for UL applications; 10% to 93% noncondensing for EN54 applications.
    • Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x 1.25" (31.75 mm) deep.
    • Shipping weight: 0.76 lb. (0.345 kg) including packaging.

    Mounting options
    – CHS-6 chassis: Up to 6 modules.
    – BB-25 cabinet: Up to 6 modules.
    – BB-XP cabinet: One or two modules.
    – CAB-4 Series cabinet: See DN-6857.
    – EQ Cabinet Series: See DN-60229.

    • Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).
    • Power-limited circuits must employ type FPL, FPLR, or FPLP cable as required by Article 760 of the NEC.
    • XP10-M is shipped in Class B position; remove shunt for Class A operation.
    • Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent.
    • Maximum IDC wiring resistance: 1500 ohms.
    • Maximum IDC voltage: 10.2 VDC.
    • Maximum IDC current: 240 μA.

     

  • Certification

    • UL Listed: S635
    • ULC Listed: S635 (XP10-MA)
    • CSFM approved: 7300-0028:219
    • FM approved
    • MEA approved: 43-02-E
    • Maryland State Fire Marshal approved: Permit #2106

     

     