NOTI•FIRE•NET™

  • General Description

    • NOTI•FIRE•NET™ is the interface which allows NOTIFIER Intelligent Fire Alarm Control Panels to form a network. Each local control panel (network node) maintains its own area of protection, while monitoring and controlling other areas (other network nodes).
    • Local information is displayed at each network node. In areas such as a security office, where the entire network must be monitored, network annunciators are available.

  • Features

    • Fiber optic (multi-mode), wire, or combination wire/fiber communications path.
    • NFPA Style 4 or Style 7 network operation.
    •  Based on proven ARCNET® technology.
    •  True peer-to-peer communications. Each node stores its own program and communicates equally with all other nodes.
    •  Token-passing non-collision protocol.
    •  No “master” polling computer or other central weak link.
    •  Inherently regenerative system. Each node acts as a repeater to reshape and regenerate data signals. Failure of any node does not affect any other node/communications among surviving nodes.
    • High-speed data communications (312,500 BPS) operates several times as fast as competitive networks.
    •  Simple plug-in module, the SIB-NET, connects AM2020/ AFP1010. The NAM-232 connects AFP-200, AFP-300/400 panels anywhere on the network. The NCM connects the NFS-3030, NFS-640, NCA, BACnet Gateway, and NWS.
    • Multiple Network Control Stations (ONYXWORKS®) may be placed anywhere on the network. Additional ONYXWORKS ® may be used to provide inherent “hot” backup.
    •  Multiple Network Control Annunciators (NCA) may be placed anywhere on the network. Version 5.0 does not support the INA.
    • ONYXWORKS® and JNCA display all network activity. Unlike competitive systems, the point display capacity is NOT hold to less than the maximum network capacity.
    • Single small-gauge twisted-pair wire (no shield necessary) for data communications path.
    •  Electrical isolation between nodes.
    • Network clock synchronization (see page 3).
    •  History buffers on NCA, ONYXWORKS® NCS, NFS-3030, NFS-640, AFP-1010, AM2020, AFP-200, AFP-300, and AFP-400 Intelligent Fire Control Panels.
    •  Powerful Cooperative-Control-by-Event allows point(s) on one node to activate point(s) on other nodes. Any input can turn on any output, network-wide.

     

  • Data Sheet

    Download

    NOTI•FIRE•NET™

     

     

     

  • Specification

    • ONYXWORKS®. See ONYXWORKS® data sheet, DN-7048.
    • NCA Network Control Annunciator. See NCA data sheet,DN-6858.
    •  NAM-232 Network Interface Board. See NAM-232 data sheet, DN-5331.
      SIB-NET Serial Interface Board
      – NFN interface: standard MIB slot.
      – EIA-232 terminal ports (2): 2,400 baud, isolated.
      – EIA-232 printer ports (2): 2,400 baud, isolated
      – EIA-485 ACS port: 20,833 baud, isolated.
      – Size: 8.0" x 8.0" (203.2 x 203.2 mm).
      – Compatible panels: AM2020, AFP1010.
      MIB-W Media Interface Board
      – Data rate (bits per second): 312,500.
      – Maximum wire distance: 3,000 feet (914.4 meters), two channels.
      – Wiring type: twisted pair.
      – Wire size: 14 AWG (2.0 mm²) to 18 AWG (0.75 mm²).
      – Board size: 3.5" (88.9 mm) x 5.0" (127.0 mm).
      MIB-F Media Interface Board
      – Data rate (bits per second): 312,500.
      – Fiber distance: 10 dB loss, two channels.
      – Fiber type: dual, Plenum grade.
      – Fiber size: 62.5 μm/125 μm;
      – Wavelength: 850 nM.
      – Connector type: ST®.
      – Board size: 3.5" (88.9 mm) x 5.0" (127.0 mm)
      • MIB-WF Media Interface Board. Specifications: same as MIB-W plus MIB-F; one channel wire, one channel fiber.
      RPT-W, RPT-F, RPT-WF Repeaters.
      – Wire/fiber specifications: same as MIB-W and MIB-F.
      – Board size: 4.4" (111.76 mm) x 6.5" (165.1 mm).

        NCM-W Network Communications Module
    – See NCM-W and NCM-F data sheet, DN-6861.
    – Compatible panels: NFS-640, NFS-3030.

       NCM-F Network Communications Module
    – See NCM-W and NCM-F data sheet, DN-6861.
    – Compatible panels: NFS-640, NFS-3030.
    • BACnet Gateway. See BACnet Gateway data sheet, DN-6877.
    • NWS NOTI•FIRE•NET™ Web Server. See NWS data sheet, DN-6928.

     



  • Certification

    • UL Listed: S635
    • ULC Listed: CS118

     