  • General Description

    • High-Speed NOTI•FIRE•NET (HS-NFN) is the interface which allows NOTIFIER Intelligent Fire Alarm Control Panels to form a network. Each local control panel (network node) maintains its own area of protection, while monitoring and controlling other areas (other network nodes). Allows for up to 200 node addresses.
    • Local information is displayed at each network node. In areas such as a security office, where the entire network must be monitored, network annunciators are available.
      NOTE: High-Speed Noti•Fire•Net is NOT compatible with Noti•Fire•Net.

     

     

     

  • Features

    • Multi-mode fiber optic (MF), single-mode fiber optic (SF), wire (W), or a combination of W/MF/SF communications path.
    • NFPA Style 4 or Style 7 network operation.
    • True peer-to-peer communications. Each node stores its own program and communicates equally with all other nodes.
    • No “master” polling computer or other central weak link.
    • Inherently regenerative system. Each node acts as a repeater to reshape and regenerate data signals. Failure of any node does not affect any other node/communications among surviving nodes.
    • High-speed data communications (12 Mb wire, 100 Mb MF/ SF fiber) operates several times as fast as competitive networks.
    • Simple plug-in module. The HS-NCM connects the NFS2- 3030, NFS-3030, NFS2-640, NFS-640, NFS-320, NCA-2, NCA, DVC, ONYXWorks, BACnet Gateway, and NWS/ NWS-3.
    • Multiple ONYXWorks® may be placed anywhere on the network. Additional ONYXWorks may be used to provide inherent “hot” backup.
    • Multiple Network Control Annunciators (NCA/NCA-2) may be placed anywhere on the network.
    • ONYXWorks, NCA and NCA-2 display all network activity. Unlike competitive systems, the point display capacity is NOT held to less than the maximum network capacity.
    • Single small-gauge (18 AWG to 14 AWG) twisted-pair wire (no shield necessary) for data communications path.
    • Electrical isolation between nodes.
    • Network clock synchronization (see page 3).
    • History Buffers on NCA-2, NCA, ONYXWorks, NFS2-3030, NFS-3030, NFS2-640, NFS-640, and NFS-320 Intelligent Fire Control Panels.
    • Powerful Cooperative-Control-by-Event allows point(s) on one node to activate point(s) on other nodes. Any input can turn on any output, network-wide.

     

  • Data Sheet

    Download

    High-Speed Noti•Fire•Net Network Systems

     

     

  • Specification

    • ONYXWorks Workstation See ONYXWorks data sheet, DN-7048.
    • NCA Network Control Annunciator See NCA data sheet, DN-6858.
    • NCA-2 ONYX Network Control Annunciator See NCA-2 data sheet, DN-7047
    • HS-NCM-W/MF/SF/WMF/WSF/MFSF Network Communications Module See High-Speed Network Communications Modules data sheet, DN-60454. Compatible panels: NFS-320, NFS-640, NFS2-640, NFS-3030. NFS2-3030.
    • BACnet Gateway See BACNET-GW-3 data sheet, DN-6877.
    • NWS-3 NOTI•FIRE•NET™ Web Server See NWS-3 data sheet, DN-6928.
    • NFN-GW-EM-3, DN-7060
    • DVC, DN-7045
    • Modbus Gateway See MODBUS-GW datasheet, DN-60533

     

  • Certification

    • UL/ULC Listed: S635 (HS-NCM, Printer), S5526 (ONYXWorks)
    • FM Approved (HS-NCM)
    • CSFM: 7300-0028:0257 (HS-NCM), 7300-1525:0103:0103(ONYXWorks)