- General Description
- The SFP-10UD is a ten-zone FACP (Fire Alarm Control Panel) . These control panels provide reliable fire signaling protection for small to medium-sized commercial, industrial, and institutional buildings. Both panels include built-in communicators for Central Station Service and remote upload/download.
- Each of these FACPs is compatible with System Sensor’s microprocessor-based i3 series detectors. These conventional smoke detectors can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory “freeze” signal when the ambient temperature falls below the detector rating. Additionally, both the SFP- 10UD is compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterflow devices, tamper switches, and other normally-open contact devices. Refer to the Notifier Device Compatibility Document for a complete listing of compatible devices.
- Outputs include four NACs (Notification Appliance Circuits),three programmable Form-C relays (factory programmed forAlarm, Trouble, and Supervisory) and 24 VDC special application resettable and nonresettable power outputs. The FACPs supervise all wiring, AC voltage, battery level and telephone line integrity.
- Activation of a compatible smoke detector or any normallyopen fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo sounder at the FACP, activate the communicator and FACP alarm relay, and operate an optional module used to notify a remote station or initiate an auxiliary control function.
- The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet saving the monthly cost of two telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line.
- Features
• Listed to UL Standard 864, 9th edition.
• Built-in DACT (Digital Alarm Communicator/Transmitter).
• Style B (Class B) IDC (Initiating Device Circuit)
– SFP-10UD - ten IDCs.
Style Y (Class B) NAC (Notification Appliance Circuit) - special application power
– SFP-10UD - four NACs.
Notification Appliances may be programmed as– Silence Inhibit.
– Auto-Silence.– Strobe Synchronization for System Sensor, Wheelock,
Gentex, Faraday, or Amseco devices.
– Selective Silence (horn-strobe mute).
– Temporal or Steady Signal.
– Silenceable or Nonsilenceable.
• Optional N-CAC-5X Style Z (Class A) Converter Module for NACs and IDCs (2 required for SFP-10UD).
• Form-C Relays for Alarm, Trouble and Supervisory - Contact Ratings 2.0 A@ 30 VDC or 30 VAC (resistive).
• 7.0 SFP-10UD total system current.
• Optional Dress Panel DP-51050 (red)
• Optional Dress Panel DP-51050B (black).
• Optional Trim Ring TR-CE/-B for semi-flush mounting.
• 24 volt operation.
• Low AC voltage sense.
• Alarm Verification.
• PAS (Positive Alarm Sequence).
• Automatic battery trickle charger.
Up to eight ANN-BUS annunciators:
– Optional 8 zone Relay Module N-ANN-RLY.
– Optional LED Annunciator Module N-ANN-LED,
– Optional Remote LCD Annunciator N-ANN-80.
– Optional Remote Printer Gateway N-ANN-S/PG.
– Optional LED Annunciator Driver N-ANN-I/O.
• Optional 4XTM module (conventional reverse polarity/city box transmitter). - Data Sheet
Download
SFP-10UD Ten Zone Fire Alarm Control Panel
- Specification
• SFP-10UD(R) (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 A
• SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 A.
• Wire size: minimum 14 AWG (2.0 mm2) with 600 V insulation,supervised, nonpower-limited - Certification
• UL Listed: File S635
• FM Approved
• CSFM: 7165-0028:246
• MEA: MEA: 333-07-E