SFP-2402 2-Zone Fire Alarm Control Panel

  • General Description

    • The Notifier SFP-2402 and SFP-2402E Fire Alarm Control Panels (FACPs) bring the latest in microprocessor technology to conventional fire controls. The SFP-2402 is compatible with the i³™ smoke detectors from System Sensor with drift compensation, maintenance alert, and freeze warning. Automatic synchronization of audio/visual devices with three selections for manufacturer protocol. The Notification Appliance Circuit (NAC) protocol can silence audible devices while strobes continue to flash, using a single pair of wires.

  • Features

    • Two Style B (Class B) Initiating Device Circuits (IDCs).
    • One Style Y (Class B) NAC.
    • 24 VDC.
    i³™ Technology features:
    – Drift compensation automatically adjusts detector sensitivity and increases resistance to false alarms caused by dust accumulation.
    – Maintenance Alert LEDs (per zone) warn of excessive dirt accumulation, preventing false alarms (meets NFPA 72 requirements).
    – Detector sensitivity is automatically measured by the detector, which automatically adjusts its sensitivity back to the factory settings when it becomes more sensitive due to contaminants settling in the chamber.
    – Wireless handheld sensitivity meter eliminates the need for voltmeters, magnets, and a physical connection to the detector. The reader displays sensitivity in terms of percent per foot obscuration and provides text status indication.
    – Supervisory LED (per zone) provides warning if a detector senses temperature approaching freezing.
    – Special test protocol and LED indication allows quick test of all detectors without need for a ladder.
    NAC synchronization features:
    – Synchronization of standard ANSI audible signals

     

  • Data Sheet

    Download

    SFP-2402 2-Zone Fire Alarm Control Panel

     

     

     

  • Specification

    AC POWER — TB8
    • SFP-2402: 120 VAC, 50/60 Hz, 2.3 A.
    • SFP-2402E: 240 VAC, 50 Hz, 1.15 A.
    • Wire Size: Minimum 14 AWG (2.0 mm²) with 600 V insulation.
    BATTERY (SEALED LEAD-ACID ONLY) — J8
    • Maximum charging circuit: normal flat charge 27.6 VCD @0.8 A.
    • Maximum battery charger capacity: 18.0 AH battery

    (two 7.0 AH batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the Notifier BB-17). INITIATING DEVICE CIRCUIT — TB3
    • Alarm zones 1 & 2.
    • Power-limited circuitry.
    • Operation: all zones Style B (Class B).
    • Normal operating voltage: nominal 20 VDC.
    • Alarm current: 15 mA minimum.
    • Short-circuit current: 40 mA maximum.
    • Maximum loop resistance: 100 ohms.
    • End-of-line resistor: 4.7K ohm, ½ watt (P/N 71252).
    • Standby current: 4 mA.
    • Compatible devices: refer to the Notifier Device Compatibility
    Document no. 15378 for a complete list of compatibledevices.

     

     

  • Certification

    • UL Listed: S635.
    • MEA: 297-01-E Vol. II.
    • CSFM: 7165-0028:220.

     