- MAYSUN ENGINEERING COMPANY LIMITED - https://maysun.com.hk -
FLM‑420‑RLV1 Relay Interface Modules Low Voltage
- General Description
- The FLM‑420‑RLV1 Relay Interface Modules Low Voltage feature a changeover contact relay for providing a potential-free output contact. They are 2‑wire LSN elements. When connected to the fire panels FPA‑5000 and FPA‑1200, the interface module offers the enhanced functionality of LSN improved technology.
- Features
- Maximum switching current of 5 A/30 V DC (type DIN rail), 1 A/30 V DC (type in-built), 0.5 A/42.4 V AC (both variants)
- Low current consumption
- Maintains LSN loop functions in the event of wire interruption or short-circuit thanks to two integrated isolators
- Data Sheet
Download
FLM‑420‑RLV1 Relay Interface Modules Low Voltage
- Specification
LSN LSN input voltage 15 V DC to 33 V DC (min. to max.) Max. current consumption from LSN 1.75 mA Relay (low voltage) Normally closed, common and normally open contact (NC/COM/NO) Contact load (ohm resistive load) FLM‑420‑RLV1‑E Max. switching current and voltage 1 A / 30 V DC 0.5 A / 42.4 V AC Min. switching current and voltage 0.01 mA / 10 mV DC 0.01 mA / 10 mV AC Max. frequency AC 100 Hz Contact load (ohm resistive load) FLM‑420‑RLV1‑D Max. switching current and voltage 5 A / 30 V DC 0.5 A / 42.4 V AC Min. switching current and voltage 0.1 mA / 100 mV DC 0.1 mA / 100 mV AC Max. AC frequency 100 Hz Minimum activation time of the connected device > 20 ms Connections FLM-420-RLV1-E 12 screw terminals FLM-420-RLV1-D 6 threaded terminals Permitted wire cross-section FLM-420-RLV1-E 0.6 to 2.0 mm2 FLM-420-RLV1-D 0.6 to 3.3 mm2 Address setting FLM-420-RLV1-E 8 DIP switches FLM-420- RLV1-D 3 rotary switches Housing material FLM-420- RLV1-E ABS/PC blend FLM-420- RLV1-D with adapter PPO (Noryl) Color FLM-420- RLV1-E Signal white, RAL 9003 FLM-420- RLV1-D Off-white, similar to RAL 9002 Dimensions FLM-420- RLV1-E Approx. 50 mm x 22 mm (Ø x H) FLM-420- RLV1-D with adapter Approx. 110 x 110 x 48 mm (W x H x D) Weight Without / with packaging FLM-420- RLV1-E Approx. 35 g / 130 g FLM-420- RLV1-D Approx. 150 g / 235 g Permitted operating temperature -20 °C to +55 °C Permitted storage temperature -25 °C to +80 °C Permitted rel. humidity < 96% (non-condensing) Classes of equipment as per IEC 60950 Class III equipment Protection class as per IEC 60529 IP 30 - Certification
Article printed from MAYSUN ENGINEERING COMPANY LIMITED : https://maysun.com.hk
URL to article: https://maysun.com.hk/en/print_page/product_details/455
Click here to print.