- MAYSUN ENGINEERING COMPANY LIMITED - https://maysun.com.hk -
FCM-1 Control Module
- General Description
- FCM-1(A) Control Module: The FCM-1(A) Addressable Control Module provides Notifier intelligent fire alarm control panels a circuit for Notification Appliances (horns, strobes, speakers, etc.). Addressability allows the FCM-1(A) to be activated, either manually or through panel programming, on a select (zone or area of coverage) basis.
- Features
- Built-in type identification automatically identifies these devices to the control panel.
- Internal circuitry and relay powered directly by two-wire SLC loop. The FCM-1(A) module requires power (for horns, strobes, etc.), or audio (for speakers).
- Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated.
- LED blink may be deselected globally (affects all devices).
- High noise immunity (EMF/RFI).
- The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms).
- Wide viewing angle of LED.
- SEMS screws with clamping plates for wiring ease.
- Direct-dial entry of address 01– 159 for FlashScan loops, 01 – 99 for CLIP mode loops.
- Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z).
- The FCM-1(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit.
- Data Sheet
Download
- Specification
- Normal operating voltage: 15 to 32 VDC.
- Maximum current draw: 6.5 mA (LED on).
- Average operating current: 350 A direct poll, 375 A group poll with LED flashing, 485 A Max. (LED flashing, NAC shorted.)
- Maximum NAC Line Loss: 4 VDC.
- External supply voltage (between Terminals T10 and T11): Maximum (NAC): Regulated 24 VDC; Maximum (Speakers): 70.7 V RMS, 50W. Drain on external supply: 1.7 mA maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply. Max NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A.
- Temperature range: 32°F to 120°F (0°C to 49°C).
- Humidity range: 10% to 93% non-condensing.
- Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box.
- Accessories: SMB500 Electrical Box; CB500 Barrier
- Certification
• UL: S635
• ULC: S3705 (A version only)
• FM Approved
• CSFM: 7300-0028:0219
• MEA: 14-00-E
• FDNY: COA #6067, #6065
Article printed from MAYSUN ENGINEERING COMPANY LIMITED : https://maysun.com.hk